| product brand name | SIRIUS |
| product designation | Auxiliary contactor |
| product type designation | 3RH2 |
| General technical data |
| size of contactor | S00 |
| product extension auxiliary switch | Yes |
| insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| degree of pollution | 3 |
| surge voltage resistance rated value | 6 kV |
| protection class IP on the front | IP20 |
| shock resistance at rectangular impulse | |
| ● at DC | 10g / 5 ms, 5g / 10 ms |
| shock resistance with sine pulse | |
| ● at DC | 15g / 5 ms, 8g / 10 ms |
| mechanical service life (operating cycles) | |
| ● of contactor typical | 30 000 000 |
| ● of the contactor with added electronically optimized auxiliary switch block typical | 5 000 000 |
| ● of the contactor with added auxiliary switch block typical | 10 000 000 |
| reference code according to IEC 81346-2 | K |
| Substance Prohibitance (Date) | 09/01/2022 |
| Ambient conditions |
| installation altitude at height above sea level maximum | 2 000 m |
| ambient temperature | |
| ● during operation | -5 … +60 °C |
| ● during storage | -25 … +80 °C |
| relative humidity minimum | 10 % |
| relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95 % |
| Main circuit |
| no-load switching frequency | |
| ● at AC | 10 000 1/h |
| ● at DC | 10 000 1/h |
| Control circuit/ Control |
| type of voltage of the control supply voltage | DC |
| control supply voltage at DC rated value | 24 V |
| operating range factor control supply voltage rated value of magnet coil at DC | |
| ● initial value | 0.8 |
| ● full-scale value | 1.1 |
| closing power of magnet coil at DC | 4 W |
| holding power of magnet coil at DC | 4 W |
| closing delay | |
| ● at DC | 30 … 100 ms |
| opening delay | |
| ● at DC | 7 … 13 ms |
| arcing time | 10 … 15 ms |
| Auxiliary circuit |
| number of NC contacts for auxiliary contacts | 1 |
| ● instantaneous contact | 1 |
| number of NO contacts for auxiliary contacts | 3 |
| ● instantaneous contact | 3 |
| identification number and letter for switching elements | 31 E |
| operational current at AC-12 maximum | 10 A |
| operational current at AC-15 | |
| ● at 230 V rated value | 10 A |
| ● at 400 V rated value | 3 A |
| ● at 500 V rated value | 2 A |
| ● at 690 V rated value | 1 A |
| operational current at 1 current path at DC-12 | |
| ● at 24 V rated value | 10 A |
| ● at 110 V rated value | 3 A |
| ● at 220 V rated value | 1 A |
| ● at 440 V rated value | 0.3 A |
| ● at 600 V rated value | 0.15 A |
| operational current with 2 current paths in series at DC-12 | |
| ● at 24 V rated value | 10 A |
| ● at 60 V rated value | 10 A |
| ● at 110 V rated value | 4 A |
| ● at 220 V rated value | 2 A |
| ● at 440 V rated value | 1.3 A |
| ● at 600 V rated value | 0.65 A |
| operational current with 3 current paths in series at DC-12 | |
| ● at 24 V rated value | 10 A |
| ● at 60 V rated value | 10 A |
| ● at 110 V rated value | 10 A |
| ● at 220 V rated value | 3.6 A |
| ● at 440 V rated value | 2.5 A |
| ● at 600 V rated value | 1.8 A |
| operating frequency at DC-12 maximum | 1 000 1/h |
| operational current at 1 current path at DC-13 | |
| ● at 24 V rated value | 10 A |
| ● at 110 V rated value | 1 A |
| ● at 220 V rated value | 0.3 A |
| ● at 440 V rated value | 0.14 A |
| ● at 600 V rated value | 0.1 A |
| operational current with 2 current paths in series at DC-13 | |
| ● at 24 V rated value | 10 A |
| ● at 60 V rated value | 3.5 A |
| ● at 110 V rated value | 1.3 A |
| ● at 220 V rated value | 0.9 A |
| ● at 440 V rated value | 0.2 A |
| ● at 600 V rated value | 0.1 A |
| operational current with 3 current paths in series at DC-13 | |
| ● at 24 V rated value | 10 A |
| ● at 60 V rated value | 4.7 A |
| ● at 110 V rated value | 3 A |
| ● at 220 V rated value | 1.2 A |
| ● at 440 V rated value | 0.5 A |
| ● at 600 V rated value | 0.1 A |
| operating frequency at DC-13 maximum | 1 000 1/h |
| design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 V | C characteristic: 6 A; 0.4 kA |
| contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| Short-circuit protection |
| design of the fuse link for short-circuit protection of the auxiliary switch required | fuse gL/gG: 10 A |
| Installation/ mounting/ dimensions |
| mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
| fastening method | screw and snap-on mounting onto 35 mm standard mounting rail |
| height | 58 mm |
| width | 45 mm |
| depth | 73 mm |
| required spacing | |
| ● with side-by-side mounting | |
| — forwards | 10 mm |
| — upwards | 10 mm |
| — downwards | 10 mm |
| — at the side | 0 mm |
| ● for grounded parts | |
| — forwards | 10 mm |
| — upwards | 10 mm |
| — at the side | 6 mm |
| — downwards | 10 mm |
| ● for live parts | |
| — forwards | 10 mm |
| — upwards | 10 mm |
| — downwards | 10 mm |
| — at the side | 6 mm |
| Connections/ Terminals |
| type of electrical connection for auxiliary and control circuit | screw-type terminals |
| connectable conductor cross-section for auxiliary contacts | |
| ● solid or stranded | 0.5 … 4 mm² |
| ● finely stranded with core end processing | 0.5 … 2.5 mm² |
| type of connectable conductor cross-sections | |
| ● for auxiliary contacts | |
| — solid or stranded | 2x (0.5 … 1.5 mm²), 2x (0.75 … 2.5 mm²), 2x 4 mm² |
| — finely stranded with core end processing | 2x (0.5 … 1.5 mm²), 2x (0.75 … 2.5 mm²) |
| ● for AWG cables for auxiliary contacts | 2x (20 … 16), 2x (18 … 14), 2x 12 |
| AWG number as coded connectable conductor cross section for auxiliary contacts | 20 … 12 |
| Safety related data |
| proportion of dangerous failures with low demand rate according to SN 31920 | 40 % |
| B10 value with high demand rate according to SN 31920 | 750 000; With 0.3 x Ie |
| failure rate [FIT] with low demand rate according to SN 31920 | 100 FIT |
| IEC 61508 |
| T1 value for proof test interval or service life according to IEC 61508 | 73 a |
| Electrical Safety |
| protection class IP on the front according to IEC 60529 | IP20 |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |